Deck permits in
Cottonwood Heights.
The entire city sits above the elevation where Salt Lake City's snow load stops applying. That changes every beam.
Do you need a permit to build a deck in Cottonwood Heights?
Yes, and the snow numbers here are nothing like the valley floor. Cottonwood Heights publishes a ground snow load of 43–57 psf for drifting and an elevation range of 4,500–5,100 ft. Salt Lake City’s 28 psf minimum applies only at or below 4,239 ft — so every address in Cottonwood Heights is above that line.
Source: Cottonwood Heights Building Codes and Standards — Design factors. Read from the city’s own document and verified .
The numbers your drawings have to use
These come straight from the city’s published design criteria. They are what a plan reviewer checks a deck against.
| Criterion | Value |
|---|---|
| Ground snow load | 43–57 psf for drifting |
| Snow load source | USU snow load study data |
| Frost depth | 30 inches |
| Seismic category | D-2 |
| Elevation range | 4,500–5,100 ft |
| Inspection note | Tinted primer required on all HVAC PVC joints |
Read the elevation line and the snow line together and the point is unmissable. The city runs from 4,500 to 5,100 feet, entirely above the 4,239 ft threshold where the valley’s 28 psf minimum stops. Cottonwood Heights sits at the mouths of Big and Little Cottonwood Canyons, and it publishes 43–57 psf for drifting — up to double the valley figure.
“For drifting” is the phrase that matters
A flat ground snow load assumes snow lies evenly. Drifting is what happens when it does not — wind piles it against a wall, a guard, or the step between a house and a deck below it.
A deck tucked against the house on the uphill side, or under a roof edge that sheds onto it, can carry far more than the nominal figure. Cottonwood Heights putting a drifting range on its design factors is a direct instruction to design for that case rather than the average one.
The city also requires the value to come from the USU snow load study for the site, so the 43–57 range is a bracket, not a number to pick from.
Two practical notes
- Frost depth 30 inches, the same as the valley — the snow load rises with elevation here but the frost figure does not.
- Seismic D-2, matching Salt Lake City and Taylorsville.
- The city publishes an unusual inspection note: tinted primer is required on all HVAC PVC joints. Not a deck item, but it tells you this is a department that checks details.
- Offices are open Monday to Thursday, 7am–5pm — a four-day week.
Who to talk to at the city
Cottonwood Heights Building Division, 2277 E Bengal Blvd, Cottonwood Heights, UT 84121. Building 801-944-7060, city 801-944-7000 · codes and standards. Open Mon–Thu 7am–5pm.
A deck designed to 28 psf does not belong in Cottonwood Heights. Every address in the city is above the elevation where that figure applies, and the published drifting range runs to 57 psf — more than double. This is the single most common under-design we would expect to see on a bench deck built by a valley crew.
We handle this part
The USU snow value for your actual address, drifting checked where the deck sits against the house or under a roof edge, footings to 30 inches, and inspections — in our quote, not an extra.